Installation, Operation and
Maintenance Manual
Oil Fired Warm Air Furnaces
WML-C AND MPL-B
(Down-Flow or Horizontal Model)
ALL INSTALLATIONS MUST MEET ALL
LOCAL, PROVINCIAL/STATE, AND
FEDERAL CODES WHICH MAY
DIFFER FROM THIS MANUAL
ECR International Limited
OLSEN Division
Read this complete manual before
beginning installation. These
instructions must be kept with the
furnace for future reference.
Przeglądanie stron 0
1 2 3 4 5 6 ... 39 40

Podsumowanie treści

Strona 1 - Oil Fired Warm Air Furnaces

Installation, Operation and Maintenance Manual Oil Fired Warm Air Furnaces WML-C AND MPL-B (Down-Flow or Horizontal Model)ALL INSTALLATIONS MUST M

Strona 2 - TABLE OF CONTENTS

30318 R4 9/9/2005 10BURNER ELECTRODES Correct positioning of the electrode tips with respect to each other, to the fuel oil nozzle, and to the rest of

Strona 3

30318 R4 9/9/2005 11used in conjunction with multi-meters with temperature measurement capabilities. The return air should be measured at a point whe

Strona 4 - Fig 1 Suspended Installation

30318 R4 9/9/2005 12should be checked to ensure that all fan speeds are operating properly. OPERATING INSTRUCTIONS Before Lighting Open all supply and

Strona 5 - CHIMNEY VENTING

30318 R4 9/9/2005 13APPENDIX A- WML-C AND MPL-B BURNER SET UP WML-C AND MPL-B furnaces may be used with the following oil burners. Please note: The B

Strona 6

30318 R4 9/9/2005 14Table A-4 Riello Balanced Flue (BF) Burner Set-Up Riello Balanced Flue Series Oil Burners (For use with sidewall vented units usin

Strona 7 - OPTIONAL SIDE WALL VENTING

30318 R4 9/9/2005 15Table A-6 Direct Drive Blower Set-Up Blower Set-Up Cooling Capacity 0.20 in. w.c. 0.50 in. w.c. Furnace Model Blower Speed Motor

Strona 8 - HEAT” if

30318 R4 9/9/2005 16Table A-9 General Dimensions (Inches) Cabinet Plenum Openings Filter Return Furnace Model Width A Depth B Height C Supply D x E

Strona 9

30318 R4 9/9/2005 17APPENDIX B: WIRING DIAGRAMS Beckett AF Burner Wiring Diagram

Strona 10 - FURNACE INSTALLATION SET

30318 R4 9/9/2005 18 Beckett AFII Burner Wiring Diagram

Strona 11 - MAINTENANCE AND SERVICE

30318 R4 9/9/2005 19Riello 40F3 and F5 Burner Wiring Diagram

Strona 12 - OPERATING INSTRUCTIONS

30318 R4 9/9/2005 2 TABLE OF CONTENTS INTRODUCTION...

Strona 13

30318 R4 9/9/2005 20Riello 40BF3 Burner Wiring Diagram

Strona 14 - PSIG 0.65 USGPH 1.5

30318 R4 9/9/2005 21OPERATION OF OIL BURNER Once the furnace flue pipe, electrical and oil line connections have been made, use the following instruct

Strona 15

30318 R4 9/9/2005 22APPENDIX C-R7184 TROUBLESHOOTING R7184 DETAILED SEQUENCE OF OPERATION (FIGURE 7) Power is applied to unit. The R7184 completes a

Strona 16 - 20-1/2 x 20

30318 R4 9/9/2005 23 R7184 INTERRUPTED ELECTRONIC OIL PRIMARY CONTROL FIGURE 7 ELECTRONIC FAN TIMER BOARD ON CONTROL PANEL FIGU

Strona 17 - APPENDIX B: WIRING DIAGRAMS

30318 R4 9/9/2005 24 IDLE STATE THERMOSTAT CALLS FOR HEAT SAFETY CHECK FOR FLAME (5 SEC.) BURNER MOTOR & IGNITOR START SOLENOID VALVE OPENS TRI

Strona 18

30318 R4 9/9/2005 25 Table C-1: ELECTRONIC FAN TIMER BOARD (EFT) DETAILED SEQUENCE OF OPERATION Mode Action System Response Thermostat calls for hea

Strona 19

30318 R4 9/9/2005 26R7184 LED DIAGNOSTIC LIGHT The LED diagnostic light has several functions. It indicates the state or mode in which the oil burner

Strona 20

30318 R4 9/9/2005 27Table C-3: R7184 TROUBLESHOOTING Condition: Burner motor does not start when there is a call for heat. Procedure Status Correcti

Strona 21 - OPERATION OF OIL BURNER

30318 R4 9/9/2005 28 Condition: Burner starts then locks out on safety with indicator light flashing at 1/2 second on, 1/2 second off. (Cont.) Proced

Strona 22

30318 R4 9/9/2005 29 TABLE C4: SYSTEM AND GENERAL TROUBLESHOOTING Problem Possible Cause Remedy Thermostat not calling for heat. Check thermostat an

Strona 23

30318 R4 9/9/2005 3 IMPROPER INSTALLATION MAY CREATE A CONDITION WHERE THE OPERATION OF THE PRODUCT COULD CAUSE PERSONAL INJURY OR PROPERTY DAMAGE. IM

Strona 24

30318 R4 9/9/2005 30 TABLE C-4: SYSTEM AND GENERAL TROUBLESHOOTING continued Problem Possible Cause Remedy Electrodes out of adjustment or defectiv

Strona 25

30318 R4 9/9/2005 31 TABLE C-4: SYSTEM AND GENERAL TROUBLESHOOTING continued Problem Possible Cause Remedy Airflow blocked or dirty air filter. Cl

Strona 26

30318 R4 9/9/2005 32 PARTS LISTING: COUNTERFLOW HORIZONTAL MODEL: WML C Ref. No. Description PART NO. 1 Right and Left Side Panel 30072L

Strona 27 - IMPORTANT

30318 R4 9/9/2005 33 PARTS LISTING: COUNTERFLOW HORIZONTAL MODEL: WML C Ref. No. Description PART NO. 31 Auxiliary Limit 60T11BOF L140º F 2

Strona 28

30318 R4 9/9/2005 34

Strona 29

30318 R4 9/9/2005 35 PARTS LISTING: COUNTERFLOW HORIZONTAL MODEL: MPL Ref. No. Description PART NO. 1a 1b Right Side Panel Left Side Panel

Strona 30

30318 R4 9/9/2005 36PARTS LISTING: COUNTERFLOW HORIZONTAL MODEL: MPL Ref. No. Description PART NO. 37 Beckett oil Burner AF76XN 30389 B

Strona 31 - FINAL CHECK OUT

30318 R4 9/9/2005 37

Strona 32

30318 R4 9/9/2005 38 HOMEOWNER’S REFERENCE TABLE Model No. Serial No. Date Installed Contractor Contact Address Postal Code Telephone No. After Hour

Strona 33

30318 R4 9/9/2005 39NOTES:

Strona 34

30318 R4 9/9/2005 4 HORIZONTAL INSTALLATION WML-C AND MPL-B furnaces models are assembled and shipped ready for installation in the down-flow position

Strona 35

30318 R4 9/9/2005 40 6800 Base Line, Wallaceburg, Ontario, N8A 5E5, Can. Tel: (519) 627-0791 Fax: (519) 627-4719 2201 Dw

Strona 36

30318 R4 9/9/2005 5through a refrigeration unit unless the unit is specifically approved for such service. Generally, a six-inch clearance between the

Strona 37

30318 R4 9/9/2005 6Fig. 2: Common Chimney Problems Table 2: Common Chimney Problems Refer to Figure 2 Key Trouble Diagnostic Remedy A Top of chim

Strona 38

30318 R4 9/9/2005 7 OPTIONAL SIDE WALL VENTING Certain WML-C AND MPL-B furnace models are manufactured to be installed as sidewall vented units. Pleas

Strona 39

30318 R4 9/9/2005 8main electrical panel; however, accessory equipment such as electronic air cleaners and humidifiers may be included on the furnace

Strona 40

30318 R4 9/9/2005 9trunk ducts. These systems may require modification to provide some resistance to the airflow to prevent over-amping of the direct